HVAC duct size calculator

Find a round duct diameter and an equivalent rectangular size from airflow and design velocity.

In shortDuct area (sq ft) = CFM ÷ velocity (feet per minute). Round diameter = √(4 × area ÷ π) × 12 inches. For a rectangular duct of the same friction, the calculator solves the equivalent diameter equation for the second side.

Calculator

From your design standard or equipment data

The side you are fixed on

Enter your numbers and press Calculate.

How the HVAC duct size works

Area = airflow ÷ velocity. 400 CFM at 700 fpm needs 0.571 sq ft, or 82.3 sq in.

Round diameter = √(4 × area ÷ π), converted to inches.

Rectangular equivalent uses the equal-friction formula De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. A rectangle with the same friction needs more area than the round duct, because corners carry air less efficiently.

A HVAC duct size example

A supply trunk must carry 400 CFM at 700 fpm. The round diameter is 10.2 inches, so the next standard size is 11 inches in this simple check (check whether your standard allows rounding down). If ceiling space limits the width to 10 inches, the equal-friction rectangle is about 10 × 9 inches.

Illustration only. Confirm sizes with your design method and local code.

When a HVAC duct size helps

Technicians and estimators use a quick sizing check in the field: is this run big enough for the airflow it needs to carry? This calculator gives the answer from two numbers, airflow and the velocity your design standard allows.

It is a quick check, not a full design. Proper residential and commercial duct design also accounts for friction rate, fittings, total external static pressure and noise. Follow the design method required in your area, such as ACCA Manual D for residential systems.

Round duct capacity at a glance

This table shows how much air standard round sizes carry at two velocities. It is handy for a field check before running the calculator for the exact number.

Round duct airflow by diameter (calculated, not a design table)
Diameter Area (sq ft) CFM at 600 fpm CFM at 900 fpm
6 in 0.196 118 177
8 in 0.349 209 314
10 in 0.545 327 491
12 in 0.785 471 707
14 in 1.069 641 962
16 in 1.396 838 1,257

The numbers are area times velocity and nothing more. Your design method sets the velocity and friction limits for each part of the system, and fittings change the picture further.

What the code expects for residential jobs

The International Residential Code, adopted with local changes in most states, requires duct systems to be sized under ACCA Manual D (section M1601.1) and the equipment to be sized from a Manual J load and Manual S selection (section M1401.3). Inspectors in many jurisdictions ask to see those reports for new systems and replacements. A velocity check like this one is useful in the field, but it does not stand in for the design documents a permit may need.

A field check, start to finish

  1. Find the airflow the run must carry. For a branch, take it from the room load in the design; for a trunk, add up the branches it feeds.
  2. Enter the velocity limit your design method allows for that type of duct. Supply branches and returns usually run slower than main trunks to keep noise down.
  3. Read the round diameter and choose a standard size.
  4. If height is tight, enter the width you can fit and read the rectangular equivalent.
  5. Write the run, size and airflow on the job sheet so the next technician knows what was installed and why.

Fictional example: a 12-inch branch on a remodel must carry 300 CFM. At 600 fpm, 300 CFM needs 0.5 sq ft, a little under the 0.545 sq ft of a 10-inch duct, so the existing 12-inch run has room to spare and the low airflow complaint is more likely a damper, a crushed flex section or a dirty coil.

What people ask about the HVAC duct size

What velocity should I use?

Use the value from the design method or standard that applies to your job. Velocity affects noise and pressure drop, and limits differ for supply trunks, branches and returns.

Why is the rectangular duct bigger than the round one?

Rectangular ducts have more surface per unit of area, so they need more cross-section to carry the same air at the same friction.

Does this replace a load calculation?

No. Airflow per room comes from a heat load calculation. This tool only sizes the duct for a given airflow.

Can I use it for flex duct?

Flex duct has higher friction than metal duct, so a simple velocity check will undersize it. Use manufacturer data.

How much airflow does a ton of cooling need?

A common rule of thumb is about 400 CFM per ton, but equipment data and the Manual S selection give the real design figure, which can be lower in humid climates.

Should return ducts be the same size as supply ducts?

Not necessarily. Returns are often sized for lower velocity to reduce noise, which makes them larger for the same airflow. Follow your design method.